abb vulnerabilities, newest first, page 5
Filter
By year: all 2026 2025 2024 2023 2022 2021
- 7.8CVE-2020-8473EPSS 0.3%
Insufficient folder permissions used by system functions in ABB System 800xA Base (version 6.1 and earlier) allow low privileged users to read, modify, add and delete system and application files. An authenticated attacker who successfully…
- 7.8CVE-2020-8472EPSS 0.3%
Insufficient folder permissions used by system functions in ABB System 800xA products OPCServer for AC800M (versions 6.0 and earlier) and Control Builder M Professional, MMSServer for AC800M, Base Software for SoftControl (version 6.1 and …
- 6.5CVE-2020-11420EPSS 1.6%
UPS Adapter CS141 before 1.90 allows Directory Traversal. An attacker with Admin or Engineer login credentials could exploit the vulnerability by manipulating variables that reference files and by doing this achieve access to files and dir…
- 8.8CVE-2020-8477EPSS 1.7%
The installations for ABB System 800xA Information Manager versions 5.1, 6.0 to 6.0.3.2 and 6.1 wrongly contain an auxiliary component. An attacker is able to use this for an XSS-like attack to an authenticated local user, which might lead…
- 7.8CVE-2020-8474EPSS 0.3%
Weak Registry permissions in ABB System 800xA Base allow low privileged users to read and modify registry settings related to control system functionality, allowing an authenticated attacker to cause system functions to stop or malfunction.
- 5.5CVE-2019-19107EPSS 0.2%
The Configuration pages in ABB Telephone Gateway TG/S 3.2 and Busch-Jaeger 6186/11 Telefon-Gateway for user profiles and services transfer the password in plaintext (although hidden when displayed).
- 9.1CVE-2019-19106EPSS 1.3%
Improper implementation of Access Control in ABB Telephone Gateway TG/S 3.2 and Busch-Jaeger 6186/11 Telefon-Gateway allows an unauthorized user to access data marked as restricted, such as viewing or editing user profiles and application …
- 5.5CVE-2019-19105EPSS 0.3%
The backup function in ABB Telephone Gateway TG/S 3.2 and Busch-Jaeger 6186/11 Telefon-Gateway saves the current settings and configuration of the application, including credentials of existing user accounts and other configuration's crede…
- 9.8CVE-2019-19104EPSS 1.4%
The web server in ABB Telephone Gateway TG/S 3.2 and Busch-Jaeger 6186/11 Telefon-Gateway allows access to different endpoints of the application without authenticating by accessing a specific uniform resource locator (URL) , violating the…
- 8.8CVE-2019-10995EPSS 0.7%
ABB CP651 HMI products revision BSP UN30 v1.76 and prior implement hidden administrative accounts that are used during the provisioning phase of the HMI interface.
- 7.5CVE-2019-18997EPSS 1.5%
The HMISimulator component of ABB PB610 Panel Builder 600 uses the readFile/writeFile interface to manipulate the work file. Path configuration in PB610 HMISimulator versions 2.8.0.424 and earlier potentially allows access to files outside…
- 7.8CVE-2019-18996EPSS 0.4%
Path settings in HMIStudio component of ABB PB610 Panel Builder 600 versions 2.8.0.424 and earlier accept DLLs outside of the program directory, potentially allowing an attacker with access to the local file system the execution of code in…
- 5.3CVE-2019-18995EPSS 2.1%
The HMISimulator component of ABB PB610 Panel Builder 600 versions 2.8.0.424 and earlier fails to validate the content-length field for HTTP requests, exposing HMISimulator to denial of service via crafted HTTP requests manipulating the co…
- 6.5CVE-2019-18994EPSS 0.6%
Due to a lack of file length check, the HMIStudio component of ABB PB610 Panel Builder 600 versions 2.8.0.424 and earlier crashes when trying to load an empty *.JPR application file. An attacker with access to the file system might be able…
- 9.8CVE-2019-18250EPSS 1.7%
In all versions of ABB Power Generation Information Manager (PGIM) and Plant Connect, the affected product is vulnerable to authentication bypass, which may allow an attacker to remotely bypass authentication and extract credentials from t…
- 8.8CVE-2019-7225EPSS 2.9%
The ABB HMI components implement hidden administrative accounts that are used during the provisioning phase of the HMI interface. These credentials allow the provisioning tool "Panel Builder 600" to flash a new interface and Tags (MODBUS c…
- 7.3CVE-2019-7227EPSS 8.4%
In the ABB IDAL FTP server, an authenticated attacker can traverse to arbitrary directories on the hard disk with "CWD ../" and then use the FTP server functionality to download and upload files. An unauthenticated attacker can take advant…
- 8.8CVE-2019-7226EPSS 5.3%
The ABB IDAL HTTP server CGI interface contains a URL that allows an unauthenticated attacker to bypass authentication and gain access to privileged functions. Specifically, /cgi/loginDefaultUser creates a session in an authenticated state…
- 8.8CVE-2019-7228EPSS 3.7%
The ABB IDAL HTTP server mishandles format strings in a username or cookie during the authentication process. Attempting to authenticate with the username %25s%25p%25x%25n will crash the server. Sending %08x.AAAA.%08x.%08x will log memory …
- 5.7CVE-2019-7231EPSS 6.7%
The ABB IDAL FTP server is vulnerable to a buffer overflow when a long string is sent by an authenticated attacker. This overflow is handled, but terminates the process. An authenticated attacker can send a FTP command string of 472 bytes …
- 8.3CVE-2019-7229EPSS 1.1%
The ABB CP635 HMI uses two different transmission methods to upgrade its firmware and its software components: "Utilization of USB/SD Card to flash the device" and "Remote provisioning process via ABB Panel Builder 600 over FTP." Neither o…
- 8.8CVE-2019-7232EPSS 52%
The ABB IDAL HTTP server is vulnerable to a buffer overflow when a long Host header is sent in a web request. The Host header value overflows a buffer and overwrites a Structured Exception Handler (SEH) address. An unauthenticated attacker…
- 8.8CVE-2019-7230EPSS 3.7%
The ABB IDAL FTP server mishandles format strings in a username during the authentication process. Attempting to authenticate with the username %s%p%x%d will crash the server. Sending %08x.AAAA.%08x.%08x will log memory content from the st…
- 7.5CVE-2019-10953EPSS 3.5%
ABB, Phoenix Contact, Schneider Electric, Siemens, WAGO - Programmable Logic Controllers, multiple versions. Researchers have found some controllers are susceptible to a denial-of-service attack due to a flood of network packets.
- 7.8CVE-2018-19008EPSS 1.6%
The TextEditor 2.0 in ABB CP400 Panel Builder versions 2.0.7.05 and earlier contain a vulnerability in the file parser of the Text Editor wherein the application doesn't properly prevent the insertion of specially crafted files which could…
- 6.5CVE-2018-17928EPSS 0.8%
The product CMS-770 (Software Versions 1.7.1 and prior)is vulnerable that an attacker can read sensitive configuration files by bypassing the user authentication mechanism.
- 4.3CVE-2018-17926EPSS 0.8%
The product M2M ETHERNET (FW Versions 2.22 and prior, ETH-FW Versions 1.01 and prior) is vulnerable in that an attacker can upload a malicious language file by bypassing the user authentication mechanism.
- 6.1CVE-2018-18997EPSS 0.9%
Pluto Safety PLC Gateway Ethernet devices in ABB GATE-E1 and GATE-E2 all versions allows an unauthenticated attacker using the administrative web interface to insert an HTML/Javascript payload into any of the device properties, which may a…
- 9.8CVE-2018-18995EPSS 2.6%
Pluto Safety PLC Gateway Ethernet devices ABB GATE-E1 and GATE-E2 all versions do not allow authentication to be configured on administrative telnet or web interfaces, which could enable various effects vectors, including conducting device…
- 7.8CVE-2018-10616EPSS 1.2%
ABB Panel Builder 800 all versions has an improper input validation vulnerability which may allow an attacker to insert and run arbitrary code on a computer where the affected product is used.
- 9.8CVE-2017-7933EPSS 1.6%
In ABB IP GATEWAY 3.39 and prior, some configuration files contain passwords stored in plain-text, which may allow an attacker to gain unauthorized access.
- 9.8CVE-2017-7931EPSS 2.5%
In ABB IP GATEWAY 3.39 and prior, by accessing a specific uniform resource locator (URL) on the web server, a malicious user is able to access the configuration files and application pages without authentication.
- 8.8CVE-2017-7906EPSS 0.6%
In ABB IP GATEWAY 3.39 and prior, the web server does not sufficiently verify that a request was performed by the authenticated user, which may allow an attacker to launch a request impersonating that user.
- 9.8CVE-2017-9664EPSS 2.5%
In ABB SREA-01 revisions A, B, C: application versions up to 3.31.5, and SREA-50 revision A: application versions up to 3.32.8, an attacker may access internal files of ABB SREA-01 and SREA-50 legacy remote monitoring tools without any aut…
- 5.8CVE-2018-5477EPSS 1.2%
An Information Exposure issue was discovered in ABB netCADOPS Web Application Version 3.4 and prior, netCADOPS Web Application Version 7.1 and prior, netCADOPS Web Application Version 7.2x and prior, netCADOPS Web Application Version 8.0 a…
- 7.5CVE-2017-7920EPSS 2.7%
An Improper Authentication issue was discovered in ABB VSN300 WiFi Logger Card versions 1.8.15 and prior, and VSN300 WiFi Logger Card for React versions 2.1.3 and prior. By accessing a specific uniform resource locator (URL) on the web ser…
- 6.5CVE-2017-7916EPSS 1.5%
A Permissions, Privileges, and Access Controls issue was discovered in ABB VSN300 WiFi Logger Card versions 1.8.15 and prior, and VSN300 WiFi Logger Card for React versions 2.1.3 and prior. The web application does not properly restrict pr…
- 3.3CVE-2016-4527EPSS 0.3%
ABB PCM600 before 2.7 improperly stores PCM600 authentication credentials, which allows local users to obtain sensitive information via unspecified vectors.
- 6.5CVE-2016-4524EPSS 0.3%
ABB PCM600 before 2.7 improperly stores OPC Server IEC61850 passwords in unspecified temporary circumstances, which allows local users to obtain sensitive information via unknown vectors.
- 3.3CVE-2016-4516EPSS 0.3%
ABB PCM600 before 2.7 improperly stores the main application password after a password change, which allows local users to obtain sensitive information via unspecified vectors.
- 2.8CVE-2016-4511EPSS 0.3%
ABB PCM600 before 2.7 uses an improper hash algorithm for the main application password, which makes it easier for local users to obtain sensitive cleartext information by leveraging read access to the ACTConfig configuration file.
- 7.2CVE-2016-2281EPSS 0.3%
Untrusted search path vulnerability in ABB Panel Builder 800 5.1 allows local users to gain privileges via a Trojan horse DLL in the current working directory.
- –CVE-2014-5430EPSS 0.4%
Untrusted search path vulnerability in ABB RobotStudio 5.6x before 5.61.02 and Test Signal Viewer 1.5 allows local users to gain privileges via a Trojan horse DLL that is accessed as a result of incorrect DLL configuration by an optional i…
- –CVE-2013-5021EPSS 2.1%
Multiple absolute path traversal vulnerabilities in National Instruments cwui.ocx, as used in National Instruments LabWindows/CVI 2012 SP1 and earlier, National Instruments LabVIEW 2012 SP1 and earlier, the Data Analysis component in ABB D…
- –CVE-2012-1801EPSS 1.6%
Multiple stack-based buffer overflows in (1) COM and (2) ActiveX controls in ABB WebWare Server, WebWare SDK, Interlink Module, S4 OPC Server, QuickTeach, RobotStudio S4, and RobotStudio Lite allow remote attackers to execute arbitrary cod…
- –CVE-2012-0245EPSS 8.1%
Multiple stack-based buffer overflows in RobNetScanHost.exe in ABB Robot Communications Runtime before 5.14.02, as used in ABB Interlink Module, IRC5 OPC Server, PC SDK, PickMaster 3 and 5, RobView 5, RobotStudio, WebWare SDK, and WebWare …
- –CVE-2008-2474EPSS 7.8%
Buffer overflow in x87 before 3.5.5 in ABB Process Communication Unit 400 (PCU400) 4.4 through 4.6 allows remote attackers to execute arbitrary code via a crafted packet using the (1) IEC60870-5-101 or (2) IEC60870-5-104 communication prot…