cve.bz

CVE-2025-6625 schneider electric: Improper Input Validation

8.7 highEPSS 0.6%

High (8.7) in schneider electric. EPSS 0.6% estimated probability of exploitation activity in the next 30 days.

On this page
CWE-20: Improper Input Validation vulnerability exists that could cause a Denial Of Service when specific crafted FTP command is sent to the device.

Severity

CVSS 4.0

8.7 high
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N

CVSS 3.1

7.5 high
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS
0.6% (unchanged from 0.5% a week ago; 0.5% 30 days ago) estimated probability of exploitation activity in the next 30 days; 49th percentile. Scored 2026-11-22. A forecast for this CVE across the internet, not for your own systems.
CISA's assessment (SSVC)
Exploitation: none · Automatable: yes · Technical impact: partial, assessed 2025-08-18. From CISA's Vulnrichment in the CVE List: whether it is exploited, whether exploiting it can be automated, and how much control it gives.
CWE
CWE-20 Improper Input Validation
OWASP Top 10
A05:2025 Injection
Published
Modified
NVD analysis
Deferred: the NVD does not plan to analyze it
Record from
the NVD, synced

Ask an AI about this CVE

Show the promptExplain CVE-2025-6625 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2025-6625?via=ask-ai-copy and https://cve.bz/cve/CVE-2025-6625?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2025-6625 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the CNA's record in the CVE List.

ProductAffected
Schneider Electric Modicon M340All versions
Schneider ELectric BMXNOR0200H: Ethernet / Serial RTU ModuleAll versions
Schneider Electric BMXNGD0100: M580 Global Data moduleAll versions
Schneider Electric BMXNOC0401: Modicon M340 X80 Ethernet Communication modulesAll versions
Schneider Electric BMXNOE0100: Modbus/TCP Ethernet Modicon M340 moduleVersions prior to 3.60
Schneider Electric BMXNOE0110: Modbus/TCP Ethernet Modicon M340 FactoryCast moduleVersions prior to 6.80

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-25-238-03Schneider Electric Modicon M340 Controller and Communication Modules (Update A)2025-08-12Critical Manufacturing, EnergyModicon M340 Firmware Versions prior to SV3.70 installed on Modicon M340 Controller, Ethernet / Serial RTU Module All versions, M580 Global Data module All versions and 3 moreModbus/TCP Ethernet Modicon M340 module Version 3.60, Modbus/TCP Ethernet Modicon M340 FactoryCast module Version 6.80, Modicon M340 Firmware Version SV3.70 installed on Modicon M340 Controller
ICSA-26-260-04Schneider Electric Modicon M340 Controller and Communication Modules2025-08-12Chemical, Commercial Facilities, Critical Manufacturing, Energy, Water and Wastewater SystemsModicon M340 Firmware Versions prior to SV3.70 installed on Modicon M340 Controller, Ethernet / Serial RTU Module All versions, M580 Global Data module All versions and 3 moreModbus/TCP Ethernet Modicon M340 module Version 3.60, Modbus/TCP Ethernet Modicon M340 FactoryCast module Version 6.80, Modicon M340 Firmware Version SV3.70 installed on Modicon M340 Controller and 1 more

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits. More on the page of CWE-20 (51).

References

Check your stackJSON