A vulnerability has been identified in POWER METER SICAM Q100 (7KG9501-0AA01-0AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q100 (7KG9501-0AA01-2AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q100 (7KG9501-0AA31-0AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q100 (7KG9501-0AA31-2AA1) (All versions >= V2.60 < V2.62), POWER METER SICAM Q200 family (All versions >= V2.70 < V2.80). Affected devices store the password for the SMTP account as plain text. This could allow an authenticated local attacker to extract it and use the configured SMTP service for arbitrary purposes.

Severity

CVSS 4.0

6.8 medium
CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N

CVSS 3.1

6.2 medium
CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
EPSS
0.1% (unchanged from 0.1% a week ago; 0.10% 30 days ago) estimated probability of exploitation activity in the next 30 days; 1st percentile. Scored 2026-11-24. A forecast for this CVE across the internet, not for your own systems.
CISA's assessment (SSVC)
Exploitation: none · Automatable: no · Technical impact: partial, assessed 2025-08-12. From CISA's Vulnrichment in the CVE List: whether it is exploited, whether exploiting it can be automated, and how much control it gives.
CWE
CWE-312 Cleartext Storage of Sensitive Information
OWASP Top 10
A06:2025 Insecure Design
Published
Modified
NVD analysis
Deferred: the NVD does not plan to analyze it
Record from
the NVD, synced

Ask an AI about this CVE

Show the promptExplain CVE-2025-40752 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2025-40752?via=ask-ai-copy and https://cve.bz/cve/CVE-2025-40752?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2025-40752 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the CNA's record in the CVE List.

ProductAffected
Siemens POWER METER SICAM Q100from V2.60 before V2.62
Siemens POWER METER SICAM Q200 familyfrom V2.70 before V2.80

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-25-226-16Siemens SICAM Q100/Q2002025-08-12Critical Manufacturing, Transportation Systems, Energy, Healthcare and Public Health, Financial Services, Government Services and FacilitiesPOWER METER SICAM Q100 (7KG9501-0AA01-0AA1), POWER METER SICAM Q100 (7KG9501-0AA01-2AA1), POWER METER SICAM Q100 (7KG9501-0AA31-0AA1) and 2 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

  • CAPEC-37 Retrieve Embedded Sensitive Data Likelihood: High · Severity: Very High

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits.