A vulnerability exists in the command handling of the IEC 61850 communication stack included in the product revisions listed as affected in this CVE. An attacker with access to IEC 61850 networks could exploit the vulnera bility by using a specially crafted 61850 packet, forcing the communication interfaces of the PM 877, CI850 and CI868 modules into fault mode or causing unavailability of the S+ Operations 61850 connectivity, resulting in a denial-of-service situation.  The System 800xA IEC61850 Connect is not affected. Note: This vulnerability does not impact on the overall availability and functionality of the S+ Operations node, only the 61850 communication function.     This issue affects AC800M (System 800xA): from 6.0.0x through 6.0.0303.0, from 6.1.0x through 6.1.0031.0, from 6.1.1x through 6.1.1004.0, from 6.1.1x through 6.1.1202.0, from 6.2.0x through 6.2.0006.0; Symphony Plus SD Series: A_0, A_1, A_2.003, A_3.005, A_4.001, B_0.005; Symphony Plus MR (Melody Rack): from 3.10 through 3.52; S+ Operations: 2.1, 2.2, 2.3, 3.3.

Severity

CVSS 4.0

7.1 high
CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N

CVSS 3.1

6.5 medium
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS
0.2% (unchanged from 0.2% a week ago; 0.2% 30 days ago) estimated probability of exploitation activity in the next 30 days; 9th percentile. Scored 2026-11-15. A forecast for this CVE across the internet, not for your own systems.
CISA's assessment (SSVC)
Exploitation: none · Automatable: no · Technical impact: partial, assessed 2026-04-13. From CISA's Vulnrichment in the CVE List: whether it is exploited, whether exploiting it can be automated, and how much control it gives.
CWE
CWE-1284 Improper Validation of Specified Quantity in Input
Published
Modified
NVD analysis
Deferred: the NVD does not plan to analyze it
Record from
the NVD, synced

Ask an AI about this CVE

Show the promptExplain CVE-2025-3756 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2025-3756?via=ask-ai-copy and https://cve.bz/cve/CVE-2025-3756?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2025-3756 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Badge for a README or a site

CVE-2025-3756

An image that stays current: it is drawn from the data each time it is fetched (a host that proxies images, as GitHub does, may show its copy for a while). Markdown:

[![CVE-2025-3756](https://cve.bz/cve/badge/CVE-2025-3756.svg)](https://cve.bz/cve/CVE-2025-3756)

HTML:

<a href="https://cve.bz/cve/CVE-2025-3756"><img src="https://cve.bz/cve/badge/CVE-2025-3756.svg" alt="CVE-2025-3756"></a>

Affected

  • abb:ac800m (system 800xa)
  • abb:s+ operations
  • abb:symphony plus mr (melody rack)
  • abb:symphony plus sd series

Versions

From the CNA's record in the CVE List.

ProductAffected
ABB AC800M (System 800xA)from 6.0.0x through 6.0.0303.0
ABB AC800M (System 800xA)from 6.1.0x through 6.1.0031.0
ABB AC800M (System 800xA)from 6.1.1x through 6.1.1004.0
ABB AC800M (System 800xA)from 6.1.1x through 6.1.1202.0
ABB AC800M (System 800xA)from 6.2.0x through 6.2.0006.0
ABB Symphony Plus SD SeriesA_0
ABB Symphony Plus SD SeriesA_1
ABB Symphony Plus SD SeriesA_2.003
ABB Symphony Plus SD SeriesA_3.005
ABB Symphony Plus SD SeriesA_4.001
ABB Symphony Plus SD SeriesB_0.005
ABB Symphony Plus MR (Melody Rack)from 3.10 through 3.52
ABB S+ Operations2.1
ABB S+ Operations2.2
ABB S+ Operations2.3
ABB S+ Operations3.3

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-26-120-01ABB System 800xA, Symphony Plus IEC 618502026-04-13Chemical, Critical Manufacturing, Energy, Water and Wastewater, Water and WastewaterABB Firmware <=6.0.0303.0 (AC800M version 6.0.0-x) installed on ABB AC800M Product line (System 800xA) CI868 for IEC 61850 communication, ABB Firmware <=1.0031.0 (AC800M version 6.1.0-x) installed on ABB AC800M Product line (System 800xA) CI868 for IEC 61850 communication, ABB Firmware <=6.1.1004.0 AC800M version 6.1.1-0 and 6.1.1-1) installed on ABB AC800M Product line (System 800xA) CI868 for IEC 61850 communication and 13 moreABB Firmware 6.1.1-3 planned for Q2 2027 installed on ABB AC800M Product line (System 800xA) CI868 for IEC 61850 communication, ABB Firmware 7.0 released in Dec 2025 installed on ABB AC800M Product line (System 800xA) CI868 for IEC 61850 communication, ABB Firmware C_0 planned Q2 2026 installed on ABB Symphony Plus SD Series CI850 for IEC 61850 communication and 2 more