cve.bz

CVE-2025-1960 schneider electric webhmi – deployed with ecostruxure power automation system

9.8 criticalEPSS 0.5%

Critical (9.8) in schneider electric webhmi – deployed with ecostruxure power automation system. EPSS 0.5% estimated probability of exploitation activity in the next 30 days.

On this page
CWE-1188: Initialization of a Resource with an Insecure Default vulnerability exists that could cause an attacker to execute unauthorized commands when a system’s default password credentials have not been changed on first use. The default username is not displayed correctly in the WebHMI interface.

Severity

CVSS 3.1

9.8 critical
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
EPSS
0.5% (unchanged from 0.5% a week ago; 0.5% 30 days ago) estimated probability of exploitation activity in the next 30 days; 45th percentile. Scored 2026-11-23. A forecast for this CVE across the internet, not for your own systems.
CISA's assessment (SSVC)
Exploitation: none · Automatable: yes · Technical impact: total, assessed 2025-03-12. From CISA's Vulnrichment in the CVE List: whether it is exploited, whether exploiting it can be automated, and how much control it gives.
CWE
CWE-1188 Initialization of a Resource with an Insecure Default
Published
Modified
NVD analysis
Deferred: the NVD does not plan to analyze it
Record from
the NVD, synced

Ask an AI about this CVE

Show the promptExplain CVE-2025-1960 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2025-1960?via=ask-ai-copy and https://cve.bz/cve/CVE-2025-1960?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2025-1960 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the CNA's record in the CVE List.

ProductAffected
Schneider Electric WebHMI – Deployed with EcoStruxure Power Automation SystemWebHMI v4.1.0.0 and prior when deployed with EPAS User Interface

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-25-077-03Schneider Electric EcoStruxure Power Automation System2025-03-11Commercial Facilities, Critical Manufacturing, EnergySchneider Electric WebHMI version 4.1.0.0 and prior installed with Schneider Electric EPAS User Interface version 2.6.30.19 and prior, Schneider Electric WebHMI version 4.1.0.0 and prior installed with Schneider Electric EPAS User Interface version 2.6.30.19 and prior default component of Schneider Electric EcoStruxure Microgrid OperSchneider Electric WebHMI_Fix_users_for_Standard V1 applied on WebHMI version 4.1.0.0 and prior

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

  • CAPEC-665 Exploitation of Thunderbolt Protection Flaws Likelihood: Low · Severity: Very High

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits.

References

Check your stackJSON