cve.bz

CVE-2024-22039 siemens: Classic Buffer Overflow

9.8 criticalEPSS 0.8%Fix available

Critical (9.8) in siemens. EPSS 0.8% estimated probability of exploitation activity in the next 30 days.

On this page
A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions < IP8), Cerberus PRO EN Fire Panel FC72x IP6 (All versions < IP6 SR3), Cerberus PRO EN Fire Panel FC72x IP7 (All versions < IP7 SR5), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions < V3.0.6602), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.0.5016), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions < V3.2.6601), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.2.5015), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions < MP8), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions < MP6 SR3), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions < MP7 SR5), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions < V3.0.6602), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.0.5016), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions < V3.2.6601), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.2.5015), Sinteso Mobile (All versions < V3.0.0). The network communication library in affected systems does not validate the length of certain X.509 certificate attributes which might result in a stack-based buffer overflow. This could allow an unauthenticated remote attacker to execute code on the underlying operating system with root privileges.

Severity

CVSS 3.1

9.8 critical
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
EPSS
0.8% (unchanged from 0.8% a week ago; 0.8% 30 days ago) estimated probability of exploitation activity in the next 30 days; 58th percentile. Scored 2026-11-22. A forecast for this CVE across the internet, not for your own systems.
CISA's assessment (SSVC)
Exploitation: none · Automatable: yes · Technical impact: total, assessed 2024-05-21. From CISA's Vulnrichment in the CVE List: whether it is exploited, whether exploiting it can be automated, and how much control it gives.
CWE
CWE-120 Buffer Copy without Checking Size of Input (Classic Buffer Overflow)
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2024-22039 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2024-22039?via=ask-ai-copy and https://cve.bz/cve/CVE-2024-22039?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2024-22039 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the CNA's record in the CVE List.

ProductAffected
Siemens Cerberus PRO EN Engineering Toolbefore IP8
Siemens Cerberus PRO EN Fire Panel FC72x IP6before IP6 SR3
Siemens Cerberus PRO EN Fire Panel FC72x IP7before IP7 SR5
Siemens Cerberus PRO EN X200 Cloud Distribution IP7before V3.0.6602
Siemens Cerberus PRO EN X200 Cloud Distribution IP8before V4.0.5016
Siemens Cerberus PRO EN X300 Cloud Distribution IP7before V3.2.6601
Siemens Cerberus PRO EN X300 Cloud Distribution IP8before V4.2.5015
Siemens Cerberus PRO UL Compact Panel FC922/924before MP4
Siemens Cerberus PRO UL Engineering Toolbefore MP4
Siemens Cerberus PRO UL X300 Cloud Distributionbefore V4.3.0001
Siemens Desigo Fire Safety UL Compact Panel FC2025/2050before MP4
Siemens Desigo Fire Safety UL Engineering Toolbefore MP4
Siemens Desigo Fire Safety UL X300 Cloud Distributionbefore V4.3.0001
Siemens Sinteso FS20 EN Engineering Toolbefore MP8
Siemens Sinteso FS20 EN Fire Panel FC20 MP6before MP6 SR3
Siemens Sinteso FS20 EN Fire Panel FC20 MP7before MP7 SR5
Siemens Sinteso FS20 EN X200 Cloud Distribution MP7before V3.0.6602
Siemens Sinteso FS20 EN X200 Cloud Distribution MP8before V4.0.5016
Siemens Sinteso FS20 EN X300 Cloud Distribution MP7before V3.2.6601
Siemens Sinteso FS20 EN X300 Cloud Distribution MP8before V4.2.5015
Siemens Sinteso Mobilebefore V3.0.0

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-24-137-12Siemens Desigo Fire Safety UL and Cerberus PRO UL Fire Protection Systems2024-05-14MultipleCerberus PRO UL Compact Panel FC922/924, Cerberus PRO UL Engineering Tool, Cerberus PRO UL X300 Cloud Distribution and 3 morenone listed
ICSA-24-074-09Siemens Sinteso EN Cerberus PRO EN Fire Protection Systems2024-03-12MultipleCerberus PRO EN Engineering Tool, Cerberus PRO EN Fire Panel FC72x IP6, Cerberus PRO EN Fire Panel FC72x IP7 and 12 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits. More on the page of CWE-120 (13).

References

Check your stackJSON