CVE-2024-10085 schneider electric

8.2 highEPSS 0.4%

High (8.2) in schneider electric. EPSS 0.4% estimated probability of exploitation activity in the next 30 days.

On this page
CWE-770: Allocation of Resources Without Limits or Throttling vulnerability exists that could cause denial of service of the OPC UA communication platform when a large number of OPC UA requests are sent to the platform.

Severity

CVSS 4.0

8.2 high
CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
EPSS
0.4% (unchanged from 0.4% a week ago; 0.3% 30 days ago) estimated probability of exploitation activity in the next 30 days; 38th percentile. Scored 2026-11-17. A forecast for this CVE across the internet, not for your own systems.
CISA's assessment (SSVC)
Exploitation: none · Automatable: no · Technical impact: partial, assessed 2026-09-01. From CISA's Vulnrichment in the CVE List: whether it is exploited, whether exploiting it can be automated, and how much control it gives.
CWE
CWE-770 Allocation of Resources Without Limits or Throttling
Published
Modified
NVD analysis
Awaiting analysis
Record from
the NVD, synced

Ask an AI about this CVE

Show the promptExplain CVE-2024-10085 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2024-10085?via=ask-ai-copy and https://cve.bz/cve/CVE-2024-10085?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2024-10085 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

  • schneider electric:ecostruxure™ modicon communication server
  • schneider electric:ecostruxure™ opc ua server expert

Versions

From the CNA's record in the CVE List.

ProductAffected
Schneider Electric EcoStruxure™ OPC UA Server ExpertVersions prior to SV2.01 SP3
Schneider Electric EcoStruxure™ Modicon Communication ServerAll versions

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-25-301-01Schneider Electric EcoStruxure2025-10-14Commercial Facilities, Critical Manufacturing, EnergyEcoStruxure OPC UA Server Expert Versions prior to SV2.01 SP3, EcoStruxure Modicon Communication Server All versionsEcoStruxure OPC UA Server Expert Version SV2.01 SP3

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits. More on the page of CWE-770 (20).

References

Check your stackJSON