cve.bz

CVE-2023-46285 siemens: Improper Input Validation

7.5 highEPSS 0.9%Fix available

High (7.5) in siemens. EPSS 0.9% estimated probability of exploitation activity in the next 30 days.

On this page
A vulnerability has been identified in Opcenter Execution Foundation (All versions < V2407), Opcenter Quality (All versions < V2312), SIMATIC PCS neo (All versions < V4.1), SINEC NMS (All versions < V2.0 SP1), Totally Integrated Automation Portal (TIA Portal) V14 (All versions), Totally Integrated Automation Portal (TIA Portal) V15.1 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 8), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 3). The affected application contains an improper input validation vulnerability that could allow an attacker to bring the service into a Denial-of-Service state by sending a specifically crafted message to 4004/tcp. The corresponding service is auto-restarted after the crash is detected by a watchdog.

Severity

CVSS 3.1

7.5 high
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS
0.9% (unchanged from 0.9% a week ago; 0.9% 30 days ago) estimated probability of exploitation activity in the next 30 days; 61st percentile. Scored 2026-11-21. A forecast for this CVE across the internet, not for your own systems.
CISA's assessment (SSVC)
Exploitation: none · Automatable: yes · Technical impact: partial, assessed 2024-01-20. From CISA's Vulnrichment in the CVE List: whether it is exploited, whether exploiting it can be automated, and how much control it gives.
CWE
CWE-20 Improper Input Validation
OWASP Top 10
A05:2025 Injection
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2023-46285 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2023-46285?via=ask-ai-copy and https://cve.bz/cve/CVE-2023-46285?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2023-46285 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the CNA's record in the CVE List.

ProductAffected
Siemens Opcenter Execution Foundationbefore V2407
Siemens Opcenter Qualitybefore V2312
Siemens SIMATIC PCS neobefore V4.1
Siemens SINEC NMSbefore V2.0 SP1
Siemens Totally Integrated Automation Portal (TIA Portal) V14all versions
Siemens Totally Integrated Automation Portal (TIA Portal) V15.1all versions
Siemens Totally Integrated Automation Portal (TIA Portal) V16all versions
Siemens Totally Integrated Automation Portal (TIA Portal) V17before V17 Update 8
Siemens Totally Integrated Automation Portal (TIA Portal) V18before V18 Update 3

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-23-348-03Siemens User Management Component (UMC)2023-12-12Critical ManufacturingOpcenter Execution Foundation, Opcenter Quality, SIMATIC PCS neo and 6 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.