A vulnerability has been identified in SIMATIC STEP 7 Safety V16 (All versions < V16 Update 7), SIMATIC STEP 7 Safety V17 (All versions < V17 Update 7), SIMATIC STEP 7 Safety V18 (All versions < V18 Update 2), SIMATIC STEP 7 V16 (All versions < V16 Update 7), SIMATIC STEP 7 V17 (All versions < V17 Update 7), SIMATIC STEP 7 V18 (All versions < V18 Update 2), SIMATIC WinCC Unified V16 (All versions < V16 Update 7), SIMATIC WinCC Unified V17 (All versions < V17 Update 7), SIMATIC WinCC Unified V18 (All versions < V18 Update 2), SIMATIC WinCC V16 (All versions < V16.7), SIMATIC WinCC V17 (All versions < V17.7), SIMATIC WinCC V18 (All versions < V18 Update 2), SIMOCODE ES V16 (All versions < V16 Update 7), SIMOCODE ES V17 (All versions < V17 Update 7), SIMOCODE ES V18 (All versions < V18 Update 2), SIMOTION SCOUT TIA V5.4 SP1 (All versions), SIMOTION SCOUT TIA V5.4 SP3 (All versions), SIMOTION SCOUT TIA V5.5 SP1 (All versions), SINAMICS Startdrive V16 (All versions), SINAMICS Startdrive V17 (All versions), SINAMICS Startdrive V18 (All versions), SIRIUS Safety ES V17 (All versions < V17 Update 7), SIRIUS Safety ES V18 (All versions < V18 Update 2), SIRIUS Soft Starter ES V17 (All versions < V17 Update 7), SIRIUS Soft Starter ES V18 (All versions < V18 Update 2), Soft Starter ES V16 (All versions < V16 Update 7), TIA Portal Cloud V3.0 (All versions < V18 Update 2). Affected applications do not properly restrict the .NET BinaryFormatter when deserializing hardware configuration profiles. This could allow an attacker to cause a type confusion and execute arbitrary code within the affected application. This is the same issue that exists for .NET BinaryFormatter https://docs.microsoft.com/en-us/visualstudio/code-quality/ca2300.

Severity

CVSS 4.0

7.0 high
CVSS:4.0/AV:L/AC:L/AT:N/PR:H/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

CVSS 3.1

6.5 medium
CVSS:3.1/AV:L/AC:L/PR:H/UI:R/S:U/C:H/I:H/A:H
EPSS
0.2% (unchanged from 0.2% a week ago; 0.2% 30 days ago) estimated probability of exploitation activity in the next 30 days; 12th percentile. Scored 2026-11-21. A forecast for this CVE across the internet, not for your own systems.
CISA's assessment (SSVC)
Exploitation: none · Automatable: no · Technical impact: total, assessed 2024-07-09. From CISA's Vulnrichment in the CVE List: whether it is exploited, whether exploiting it can be automated, and how much control it gives.
CWE
CWE-502 Deserialization of Untrusted Data
OWASP Top 10
A08:2025 Software or Data Integrity Failures
Published
Modified
NVD analysis
Deferred: the NVD does not plan to analyze it
Record from
the NVD, synced

Ask an AI about this CVE

Show the promptExplain CVE-2023-32735 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2023-32735?via=ask-ai-copy and https://cve.bz/cve/CVE-2023-32735?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2023-32735 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the CNA's record in the CVE List.

ProductAffected
Siemens SIMATIC STEP 7 Safety V16before V16 Update 7
Siemens SIMATIC STEP 7 Safety V17before V17 Update 7
Siemens SIMATIC STEP 7 Safety V18before V18 Update 2
Siemens SIMATIC STEP 7 V16before V16 Update 7
Siemens SIMATIC STEP 7 V17before V17 Update 7
Siemens SIMATIC STEP 7 V18before V18 Update 2
Siemens SIMATIC WinCC Unified V16before V16 Update 7
Siemens SIMATIC WinCC Unified V17before V17 Update 7
Siemens SIMATIC WinCC Unified V18before V18 Update 2
Siemens SIMATIC WinCC V16before V16.7
Siemens SIMATIC WinCC V17before V17.7
Siemens SIMATIC WinCC V18before V18 Update 2
Siemens SIMOCODE ES V16before V16 Update 7
Siemens SIMOCODE ES V17before V17 Update 7
Siemens SIMOCODE ES V18before V18 Update 2
Siemens SIMOTION SCOUT TIA V5.4 SP1all versions
Siemens SIMOTION SCOUT TIA V5.4 SP3all versions
Siemens SIMOTION SCOUT TIA V5.5 SP1all versions
Siemens SINAMICS Startdrive V16all versions
Siemens SINAMICS Startdrive V17all versions
Siemens SINAMICS Startdrive V18all versions
Siemens SIRIUS Safety ES V17before V17 Update 7
Siemens SIRIUS Safety ES V18before V18 Update 2
Siemens SIRIUS Soft Starter ES V17before V17 Update 7
Siemens SIRIUS Soft Starter ES V18before V18 Update 2
Siemens Soft Starter ES V16before V16 Update 7
Siemens TIA Portal Cloud V3.0before V18 Update 2

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-24-193-13Siemens TIA Portal, SIMATIC, and SIRIUS2024-07-09MultipleSIMATIC STEP 7 Safety V16, SIMATIC STEP 7 Safety V17, SIMATIC STEP 7 Safety V18 and 24 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

  • CAPEC-586 Object Injection Likelihood: Medium · Severity: High

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits.