cve.bz

CVE-2022-47391 (CoDe16) codesys: Improper Input Validation

7.5 highEPSS 1.9%

Known as CoDe16

High (7.5) in codesys. EPSS 1.9% estimated probability of exploitation activity in the next 30 days.

On this page
In multiple CODESYS products in multiple versions an unauthorized, remote attacker may use a improper input validation vulnerability to read from invalid addresses leading to a denial of service.

Severity

CVSS 3.1

7.5 high
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS
1.9% (unchanged from 1.9% a week ago; 1.9% 30 days ago) estimated probability of exploitation activity in the next 30 days; 80th percentile. Scored 2026-11-21. A forecast for this CVE across the internet, not for your own systems.
CISA's assessment (SSVC)
Exploitation: none · Automatable: yes · Technical impact: partial, assessed 2025-01-23. From CISA's Vulnrichment in the CVE List: whether it is exploited, whether exploiting it can be automated, and how much control it gives.
CWE
CWE-20 Improper Input Validation
OWASP Top 10
A05:2025 Injection
Published
Modified
NVD analysis
Analyzed
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2022-47391 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2022-47391?via=ask-ai-copy and https://cve.bz/cve/CVE-2022-47391?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2022-47391 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the CNA's record in the CVE List.

ProductAffected
CODESYS Control RTE (SL)from V0.0.0.0 before V3.5.19.0
CODESYS Control RTE (for Beckhoff CX) SLfrom V0.0.0.0 before V3.5.19.0
CODESYS Control Win (SL)from V0.0.0.0 before V3.5.19.0
CODESYS Control Runtime System Toolkitfrom V0.0.0.0 before V3.5.19.0
CODESYS Safety SIL2 Runtime Toolkitfrom V0.0.0.0 before V3.5.19.0
CODESYS Safety SIL2 PSPfrom V0.0.0.0 before V3.5.19.0
CODESYS Edge Gateway for Windowsfrom V0.0.0.0 before V3.5.19.0
CODESYS Gatewayfrom V0.0.0.0 before V3.5.19.0
CODESYS HMI (SL)from V0.0.0.0 before V3.5.19.0
CODESYS Development System V3from V0.0.0.0 before V3.5.19.0
CODESYS Control for BeagleBone SLfrom V0.0.0.0 before V4.8.0.0
CODESYS Control for emPC-A/iMX6 SLfrom V0.0.0.0 before V4.8.0.0
CODESYS Control for IOT2000 SLfrom V0.0.0.0 before V4.8.0.0
CODESYS Control for Linux SLfrom V0.0.0.0 before V4.8.0.0
CODESYS Control for PFC100 SLfrom V0.0.0.0 before V4.8.0.0
CODESYS Control for PFC200 SLfrom V0.0.0.0 before V4.8.0.0
CODESYS Control for PLCnext SLfrom V0.0.0.0 before V4.8.0.0
CODESYS Control for Raspberry Pi SLfrom V0.0.0.0 before V4.8.0.0
CODESYS Control for WAGO Touch Panels 600 SLfrom V0.0.0.0 before V4.8.0.0
CODESYS Edge Gateway for Linuxfrom V0.0.0.0 before V4.8.0.0

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-26-076-01CODESYS in Festo Automation Suite2026-02-26Critical ManufacturingFesto Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0, Festo Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10, Festo Automation Suite 2.8.0.137 installed with CODESYS Development System 3.0 and 1 moreCODESYS Development System 3.5.21.20 external component of Festo Automation Suite 2.8.0.138
ICSA-26-020-02Schneider Electric devices using CODESYS Runtime2023-07-11Commercial Facilities, Critical Manufacturing, EnergySchneider Electric HMISCU Controller All versions prior to v6.3.1, Schneider Electric Modicon Controller M241 All versions prior to v5.2.11.18, Schneider Electric Modicon Controller M251 All Versions prior to v5.2.11.18 and 12 moreSchneider Electric HMISCU Controller 6.3.1, Schneider Electric Modicon Controller M241 5.2.11.18, Schneider Electric Modicon Controller M251 5.2.11.18 and 9 more

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits. More on the page of CWE-20 (51).

References

Check your stackJSON