CVSS 3.1
8.8 highCVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:HHigh (8.8) in codesys. EPSS 0.9% estimated probability of exploitation activity in the next 30 days.
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:HExplain CVE-2022-4224 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2022-4224?via=ask-ai-copy and https://cve.bz/cve/CVE-2022-4224?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2022-4224 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.
From the CNA's record in the CVE List.
| Product | Affected |
|---|---|
| CODESYS Control RTE (SL) | from 3.0.0.0 before 3.5.19.0 |
| CODESYS Control RTE (for Beckhoff CX) SL | from 3.0.0.0 before 3.5.19.0 |
| CODESYS Control Win (SL) | from 3.0.0.0 before 3.5.19.0 |
| CODESYS Runtime Toolkit | from 3.0.0.0 before 3.5.19.0 |
| CODESYS Safety SIL2 Runtime Toolkit | from 3.0.0.0 before 3.5.19.0 |
| CODESYS Safety SIL2 PSP | from 3.0.0.0 before 3.5.19.0 |
| CODESYS HMI (SL) | from 3.0.0.0 before 3.5.19.0 |
| CODESYS Development System V3 | from 3.0.0.0 before 3.5.19.0 |
| CODESYS Control for BeagleBone SL | from 3.0.0.0 before 4.8.0.0 |
| CODESYS Control for emPC-A/iMX6 SL | from 3.0.0.0 before 4.8.0.0 |
| CODESYS Control for IOT2000 SL | from 3.0.0.0 before 4.8.0.0 |
| CODESYS Control for Linux SL | from 3.0.0.0 before 4.8.0.0 |
| CODESYS Control for PFC100 SL | from 3.0.0.0 before 4.8.0.0 |
| CODESYS Control for PFC200 SL | from 3.0.0.0 before 4.8.0.0 |
| CODESYS Control for PLCnext SL | from 3.0.0.0 before 4.8.0.0 |
| CODESYS Control for Raspberry Pi SL | from 3.0.0.0 before 4.8.0.0 |
| CODESYS Control for WAGO Touch Panels 600 SL | from 3.0.0.0 before 4.8.0.0 |
| Advisory | Title | Published | Sectors | Affected | Fixed |
|---|---|---|---|---|---|
| ICSA-26-076-01 | CODESYS in Festo Automation Suite | 2026-02-26 | Critical Manufacturing | Festo Automation Suite <2.8.0.138 installed with CODESYS Development System 3.0, Festo Automation Suite <2.8.0.138 installed with CODESYS Development System 3.5.16.10, Festo Automation Suite 2.8.0.137 installed with CODESYS Development System 3.0 and 1 more | CODESYS Development System 3.5.21.20 external component of Festo Automation Suite 2.8.0.138 |
From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.
The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits.