Critical (9.8) in powertekpdus. EPSS 1.7% chance of exploitation in the next 30 days.
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyone through the /cgi/get_param.cgi HTTP API. This leads to disclosing active session ids of currently logged-in administrators. The session id can then be reused to act as the administrator, allowing reading of the cleartext password, or reconfiguring the device.
Severity
CVSS 3.1
9.8 critical
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
EPSS
1.7% chance of exploitation in the next 30 days; higher than 77% of CVEs (scores of 2026-10-31)