cve.bz

CVE-2022-28613

7.5 highEPSS 1.0%

High (7.5). EPSS 1.0% estimated probability of exploitation activity in the next 30 days.

On this page
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.

Severity

CVSS 3.1

7.5 high
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS
1.0% (unchanged from 1.0% a week ago; 1.0% 30 days ago) estimated probability of exploitation activity in the next 30 days; 63rd percentile. Scored 2026-11-22. A forecast for this CVE across the internet, not for your own systems.
CWE
CWE-1284 Improper Validation of Specified Quantity in Input
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Ask an AI about this CVE

Show the promptExplain CVE-2022-28613 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2022-28613?via=ask-ai-copy and https://cve.bz/cve/CVE-2022-28613?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2022-28613 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the NVD's CPE matches.

ProductAffected
abb:rtu500_firmwarefrom 12.2.1.0 before 12.2.12.0
hitachienergy:rtu500_firmwarefrom 12.0.1.0 before 12.0.14.0
hitachienergy:rtu500_firmwarefrom 12.4.1.0 before 12.4.12.0
hitachienergy:rtu500_firmwarefrom 12.6.1.0 before 12.6.8.0
hitachienergy:rtu500_firmwarefrom 12.7.1.0 before 12.7.4.0
hitachienergy:rtu500_firmwarefrom 13.2.1.0 before 13.2.5.0

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-22-242-04Hitachi Energy RTU500 series2022-08-30EnergyRTU500 series CMU Firmware: version 12.2.*, RTU500 series CMU Firmware: version 12.6.*, RTU500 series CMU Firmware: version 12.7.* and 3 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

References

Check your stackJSON