CVE-2022-25622 siemens: Uncontrolled Resource Consumption

7.5 highEPSS 0.9%

High (7.5) in siemens. EPSS 0.9% estimated probability of exploitation activity in the next 30 days.

On this page
The PROFINET (PNIO) stack, when integrated with the Interniche IP stack, improperly handles internal resources for TCP segments where the minimum TCP-Header length is less than defined. This could allow an attacker to create a denial of service condition for TCP services on affected devices by sending specially crafted TCP segments.

Severity

CVSS 3.1

7.5 high
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS
0.9% (unchanged from 0.9% a week ago; 0.9% 30 days ago) estimated probability of exploitation activity in the next 30 days; 61st percentile. Scored 2026-11-21. A forecast for this CVE across the internet, not for your own systems.
CISA's assessment (SSVC)
Exploitation: none · Automatable: yes · Technical impact: partial, assessed 2025-04-18. From CISA's Vulnrichment in the CVE List: whether it is exploited, whether exploiting it can be automated, and how much control it gives.
CWE
CWE-400 Uncontrolled Resource Consumption
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2022-25622 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2022-25622?via=ask-ai-copy and https://cve.bz/cve/CVE-2022-25622?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2022-25622 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the CNA's record in the CVE List.

ProductAffected
Siemens SIMATIC CFU DIQbefore V2.0.0
Siemens SIMATIC CFU PAbefore V2.0.0
Siemens SIMATIC ET 200AL IM 157-1 PNAll versions
Siemens SIMATIC ET 200MP IM 155-5 PN HFV4.2.0 and later
Siemens SIMATIC ET 200pro IM 154-8 PN/DP CPUAll versions < V3.2.19
Siemens SIMATIC ET 200pro IM 154-8F PN/DP CPUAll versions < V3.2.19
Siemens SIMATIC ET 200pro IM 154-8FX PN/DP CPUAll versions < V3.2.19
Siemens SIMATIC ET 200S IM 151-8 PN/DP CPUAll versions < V3.2.19
Siemens SIMATIC ET 200S IM 151-8F PN/DP CPUAll versions < V3.2.19
Siemens SIMATIC ET 200SP IM 155-6 MF HFall versions
Siemens SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)All versions
Siemens SIMATIC ET 200SP IM 155-6 PN HFV4.2.0 and later
Siemens SIMATIC ET 200SP IM 155-6 PN/2 HFV4.2.0 and later
Siemens SIMATIC ET 200SP IM 155-6 PN/3 HFV4.2.0 and later
Siemens SIMATIC ET200ecoPN, AI 8xRTD/TC, M12-Lfrom V5.1.1 before V5.1.2
Siemens SIMATIC ET200ecoPN, CM 4x IO-Link, M12-Lfrom V5.1.1 before V5.1.2
Siemens SIMATIC ET200ecoPN, CM 8x IO-Link, M12-Lfrom V5.1.1 before V5.1.2
Siemens SIMATIC ET200ecoPN, DI 16x24VDC, M12-Lfrom V5.1.1 before V5.1.2
Siemens SIMATIC ET200ecoPN, DI 8x24VDC, M12-Lfrom V5.1.1 before V5.1.2
Siemens SIMATIC ET200ecoPN, DIQ 16x24VDC/2A, M12-Lfrom V5.1.1 before V5.1.3
Siemens SIMATIC ET200ecoPN, DQ 8x24VDC/0,5A, M12-Lfrom V5.1.1 before V5.1.2
Siemens SIMATIC ET200ecoPN, DQ 8x24VDC/2A, M12-Lfrom V5.1.1 before V5.1.2
Siemens SIMATIC PN/MF CouplerAll versions
Siemens SIMATIC PN/PN CouplerAll versions >= 4.2
Siemens SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)All versions < V2.0.0
Siemens SIMATIC S7-300 CPU 314C-2 PN/DPAll versions < V3.3.19
Siemens SIMATIC S7-300 CPU 315-2 PN/DPAll versions < V3.2.19
Siemens SIMATIC S7-300 CPU 315F-2 PN/DPAll versions < V3.2.19
Siemens SIMATIC S7-300 CPU 315T-3 PN/DPAll versions < V3.2.19
Siemens SIMATIC S7-300 CPU 317-2 PN/DPAll versions < V3.2.19
Siemens SIMATIC S7-300 CPU 317F-2 PN/DPAll versions < V3.2.19
Siemens SIMATIC S7-300 CPU 317T-3 PN/DPAll versions < V3.2.19
Siemens SIMATIC S7-300 CPU 317TF-3 PN/DPAll versions < V3.2.19
Siemens SIMATIC S7-300 CPU 319-3 PN/DPAll versions < V3.2.19
Siemens SIMATIC S7-300 CPU 319F-3 PN/DPAll versions < V3.2.19
Siemens SIMATIC S7-400 CPU 412-2 PN V7all versions
Siemens SIMATIC S7-400 CPU 414-3 PN/DP V7all versions
Siemens SIMATIC S7-400 CPU 414F-3 PN/DP V7all versions
Siemens SIMATIC S7-400 CPU 416-3 PN/DP V7all versions
Siemens SIMATIC S7-400 CPU 416F-3 PN/DP V7all versions
Siemens SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants)before V6.0.10
Siemens SIMATIC S7-410 V10 CPU family (incl. SIPLUS variants)All versions < V10.1.1
Siemens SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants)before V8.2.3
Siemens SIMATIC TDC CP51M1before V1.1.10
Siemens SIMATIC TDC CPU555before V1.2.1
Siemens SIMATIC WinAC RTX 2010All versions
Siemens SIMATIC WinAC RTX F 2010All versions
Siemens SINAMICS DCMbefore V1.5 SP1
Siemens SINAMICS G110Mbefore V4.7.14
Siemens SINAMICS G115Dbefore V4.7.14
Siemens SINAMICS G120 (incl. SIPLUS variants)before V4.7 SP14
Siemens SINAMICS G130before V5.2.3.13
Siemens SINAMICS G150before V5.2.3.13
Siemens SINAMICS S110all versions
Siemens SINAMICS S120 (incl. SIPLUS variants)before V5.2 SP3 HF13
Siemens SINAMICS S150before V5.2.3.13
Siemens SINAMICS S210 (6SL5...)before V5.2 SP3 HF18
Siemens SINAMICS V90before V1.04.04
Siemens SIPLUS ET 200MP IM 155-5 PN HFV4.2.0 and later
Siemens SIPLUS ET 200MP IM 155-5 PN HF T1 RAILV4.2.0 and later
Siemens SIPLUS ET 200S IM 151-8 PN/DP CPUAll versions < V3.2.19
Siemens SIPLUS ET 200S IM 151-8F PN/DP CPUAll versions < V3.2.19
Siemens SIPLUS ET 200SP IM 155-6 PN HFV4.2.0 and later
Siemens SIPLUS ET 200SP IM 155-6 PN HF T1 RAILV4.2.0 and later
Siemens SIPLUS ET 200SP IM 155-6 PN HF TX RAILV4.2.0 and later
Siemens SIPLUS HCS4200 CIM4210All versions
Siemens SIPLUS HCS4200 CIM4210CAll versions
Siemens SIPLUS HCS4300 CIM4310All versions
Siemens SIPLUS NET PN/PN CouplerAll versions >= 4.2
Siemens SIPLUS S7-300 CPU 314C-2 PN/DPAll versions < V3.3.19
Siemens SIPLUS S7-300 CPU 315-2 PN/DPAll versions < V3.2.19
Siemens SIPLUS S7-300 CPU 315F-2 PN/DPAll versions < V3.2.19
Siemens SIPLUS S7-300 CPU 317-2 PN/DPAll versions < V3.2.19
Siemens SIPLUS S7-300 CPU 317F-2 PN/DPAll versions < V3.2.19
Siemens SIPLUS S7-400 CPU 414-3 PN/DP V7all versions
Siemens SIPLUS S7-400 CPU 416-3 PN/DP V7all versions

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-22-104-06Siemens PROFINET Stack Integrated on Interniche Stack2022-04-12Critical Manufacturing, Transportation Systems, Energy, Healthcare and Public Health, Financial Services, Government Services and FacilitiesSIMATIC CFU DIQ (6ES7655-5PX31-1XX0), SIMATIC CFU PA (6ES7655-5PX11-0XX0), SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) and 47 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

  • CAPEC-147 XML Ping of the Death Likelihood: Low · Severity: Medium
  • CAPEC-227 Sustained Client Engagement
  • CAPEC-492 Regular Expression Exponential Blowup

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits.

References

Check your stackJSON