cve.bz

CVE-2022-2277 hitachienergy microscada x sys600

7.5 highEPSS 0.8%

High (7.5) in hitachienergy microscada x sys600. EPSS 0.8% estimated probability of exploitation activity in the next 30 days.

On this page
Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP system. By default, ICCP is not configured and not enabled. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10.2 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*

Severity

CVSS 3.1

7.5 high
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS
0.8% (unchanged from 0.8% a week ago; 0.8% 30 days ago) estimated probability of exploitation activity in the next 30 days; 57th percentile. Scored 2026-11-22. A forecast for this CVE across the internet, not for your own systems.
CISA's assessment (SSVC)
Exploitation: none · Automatable: yes · Technical impact: partial, assessed 2025-06-04. From CISA's Vulnrichment in the CVE List: whether it is exploited, whether exploiting it can be automated, and how much control it gives.
CWE
CWE-1284 Improper Validation of Specified Quantity in Input
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Ask an AI about this CVE

Show the promptExplain CVE-2022-2277 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2022-2277?via=ask-ai-copy and https://cve.bz/cve/CVE-2022-2277?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2022-2277 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the NVD's CPE matches.

ProductAffected
hitachienergy:microscada_x_sys600from 10.2 through 10.3.1

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-23-059-02Hitachi Energy Gateway Station2023-03-06EnergyGateway Station (GWS): 3.0.0.0, Gateway Station (GWS): 3.1.0.0, Gateway Station (GWS): 3.2.0.0none listed
ICSA-22-272-01Hitachi Energy MicroSCADA Pro X SYS6002022-09-29EnergySYS600: 10.3.1 and earlier, SYS600: 9.4 FP2 Hotfix 4 and earlier versionsnone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

References