cve.bz

CVE-2022-22723 schneider-electric easergy p5 firmware: Classic Buffer Overflow

8.8 highEPSS 2.8%

High (8.8) in schneider-electric easergy p5 firmware. EPSS 2.8% estimated probability of exploitation activity in the next 30 days.

On this page
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could lead to a buffer overflow causing program crashes and arbitrary code execution when specially crafted packets are sent to the device over the network. Protection functions and tripping function via GOOSE can be impacted. Affected Product: Easergy P5 (All firmware versions prior to V01.401.101)

Severity

CVSS 3.1

8.8 high
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
EPSS
2.8% (unchanged from 2.8% a week ago; 2.8% 30 days ago) estimated probability of exploitation activity in the next 30 days; 87th percentile. Scored 2026-11-22. A forecast for this CVE across the internet, not for your own systems.
CWE
CWE-120 Buffer Copy without Checking Size of Input (Classic Buffer Overflow)
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2022-22723 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2022-22723?via=ask-ai-copy and https://cve.bz/cve/CVE-2022-22723?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2022-22723 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the NVD's CPE matches.

ProductAffected
schneider-electric:easergy_p5_firmwarebefore 01.401.101

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-22-055-03Schneider Electric Easergy P5 and P32022-02-24Commercial Facilities, EnergyEasergy P3: All versions prior to v30.205, Easergy P5 All firmware: versions prior to v01.401.102none listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits. More on the page of CWE-120 (13).

References

Check your stackJSON