High (7.5) in schneider-electric easergy p5 firmware. EPSS 2.4% chance of exploitation in the next 30 days.
A CWE-798: Use of Hard-coded Credentials vulnerability exists that could result in information disclosure. If an attacker were to obtain the SSH cryptographic key for the device and take active control of the local operational network connected to the product they could potentially observe and manipulate traffic associated with product configuration. Affected Product: Easergy P5 (All firmware versions prior to V01.401.101)
Severity
CVSS 3.1
7.5 high
CVSS:3.1/AV:A/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H
EPSS
2.4% chance of exploitation in the next 30 days; higher than 83% of CVEs (scores of 2026-10-31)