cve.bz

CVE-2021-31890 (NUCLEUS:13) siemens

9.1 criticalEPSS 2.2%

Known as NUCLEUS:13

Critical (9.1) in siemens. EPSS 2.2% estimated probability of exploitation activity in the next 30 days.

On this page
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), PLUSCONTROL 1st Gen (All versions), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), SIMOTICS CONNECT 400 (All versions < V1.0.0.0). The total length of an TCP payload (set in the IP header) is unchecked. This may lead to various side effects, including Information Leak and Denial-of-Service conditions, depending on the network buffer organization in memory. (FSMD-2021-0017)

Severity

CVSS 3.1

9.1 critical
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H
EPSS
2.2% (unchanged from 2.2% a week ago; 2.2% 30 days ago) estimated probability of exploitation activity in the next 30 days; 83rd percentile. Scored 2026-11-21. A forecast for this CVE across the internet, not for your own systems.
CWE
CWE-240 Improper Handling of Inconsistent Structural Elements
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2021-31890 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2021-31890?via=ask-ai-copy and https://cve.bz/cve/CVE-2021-31890?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2021-31890 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the CNA's record in the CVE List.

ProductAffected
Siemens Capital Embedded AR Classic 431-422all versions
Siemens Capital Embedded AR Classic R20-11before V2303
Siemens PLUSCONTROL 1st GenAll versions
Siemens SIMOTICS CONNECT 400All versions < V0.5.0.0
Siemens SIMOTICS CONNECT 400All versions < V1.0.0.0

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-22-069-02Siemens SIMOTICS CONNECT 4002022-03-08MultipleSIMOTICS CONNECT 400none listed
ICSA-22-013-03Siemens Energy PLUSCONTROL2022-01-11MultiplePLUSCONTROL 1st Gennone listed
ICSA-21-350-06Siemens Capital VSTAR2021-12-14Critical Manufacturing, Transportation Systems, Energy, Healthcare and Public Health, Financial Services, Government Services and FacilitiesCapital Embedded AR Classic 431-422, Capital Embedded AR Classic R20-11none listed
ICSA-21-313-03Siemens Nucleus RTOS TCP/IP Stack2021-11-09MultipleNucleus NET, Nucleus ReadyStart V3, Nucleus ReadyStart V4 and 1 morenone listed
ICSA-21-315-07Siemens Nucleus RTOS-based APOGEE and TALON Products (Update C)2021-11-09MultipleAPOGEE MBC (PPC) (BACnet), APOGEE MBC (PPC) (P2 Ethernet), APOGEE MEC (PPC) (BACnet) and 20 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

References

Check your stackJSON