cve.bz

CVE-2021-25677

5.3 mediumEPSS 1.1%

Medium (5.3) in siemens. EPSS 1.1% chance of exploitation in the next 30 days.

A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), SIMOTICS CONNECT 400 (All versions >= V0.5.0.0 < V1.0.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS client does not properly randomize DNS transaction IDs. That could allow an attacker to poison the DNS cache or spoof DNS resolving.

Severity

CVSS 3.1

5.3 medium
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N
EPSS
1.1% chance of exploitation in the next 30 days; higher than 64% of CVEs (scores of 2026-11-01)
CWE
CWE-330
Published
Modified
Record from
the NVD, synced

Affected

References

Check your stackJSON