cve.bz

CVE-2021-20595 mitsubishi

8.2 highEPSS 1.8%

High (8.2) in mitsubishi. EPSS 1.8% estimated probability of exploitation activity in the next 30 days.

On this page
Improper Restriction of XML External Entity Reference vulnerability in Mitsubishi Electric Air Conditioning System/Centralized Controllers (G-50A Ver.3.35 and prior, GB-50A Ver.3.35 and prior, GB-24A Ver.9.11 and prior, AG-150A-A Ver.3.20 and prior, AG-150A-J Ver.3.20 and prior, GB-50ADA-A Ver.3.20 and prior, GB-50ADA-J Ver.3.20 and prior, EB-50GU-A Ver 7.09 and prior, EB-50GU-J Ver 7.09 and prior, AE-200A Ver 7.93 and prior, AE-200E Ver 7.93 and prior, AE-50A Ver 7.93 and prior, AE-50E Ver 7.93 and prior, EW-50A Ver 7.93 and prior, EW-50E Ver 7.93 and prior, TE-200A Ver 7.93 and prior, TE-50A Ver 7.93 and prior, TW-50A Ver 7.93 and prior, CMS-RMD-J Ver.1.30 and prior), Air Conditioning System/Expansion Controllers (PAC-YG50ECA Ver.2.20 and prior) and Air Conditioning System/BM adapter(BAC-HD150 Ver.2.21 and prior) allows a remote unauthenticated attacker to disclose some of data in the air conditioning system or cause a DoS condition by sending specially crafted packets.

Severity

CVSS 3.1

8.2 high
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H
EPSS
1.8% (unchanged from 1.8% a week ago; 1.8% 30 days ago) estimated probability of exploitation activity in the next 30 days; 79th percentile. Scored 2026-11-22. A forecast for this CVE across the internet, not for your own systems.
CWE
CWE-611 Improper Restriction of XML External Entity Reference
OWASP Top 10
A02:2025 Security Misconfiguration
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2021-20595 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2021-20595?via=ask-ai-copy and https://cve.bz/cve/CVE-2021-20595?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2021-20595 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the NVD's CPE matches.

ProductAffected
mitsubishi:g-50a_firmwarefrom 2.50 through 3.35
mitsubishi:gb-50a_firmwarefrom 2.50 through 3.35
mitsubishi:ag-150a-a_firmwarethrough 3.20
mitsubishi:ag-150a-j_firmwarethrough 3.20
mitsubishi:gb-50ada-a_firmwarethrough 3.20
mitsubishi:gb-50ada-j_firmwarethrough 3.20
mitsubishi:eb-50gu-a_firmwarethrough 7.09
mitsubishi:eb-50gu-j_firmwarethrough 7.09
mitsubishi:ae-200a_firmwarethrough 7.93
mitsubishi:ae-200e_firmwarethrough 7.93
mitsubishi:ae-50a_firmwarethrough 7.93
mitsubishi:ae-50e_firmwarethrough 7.93
mitsubishi:ew-50a_firmwarethrough 7.93
mitsubishi:ew-50e_firmwarethrough 7.93
mitsubishi:te-200a_firmwarethrough 7.93
mitsubishi:te-50a_firmwarethrough 7.93
mitsubishi:tw-50a_firmwarethrough 7.93
mitsubishi:cms-rmd-j_firmwarethrough 1.30
mitsubishi:pac-yg50eca_firmwarethrough 2.20

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-21-182-05Mitsubishi Electric Air Conditioning Systems2021-07-01Commercial FacilitiesGB-50ADA-J: Versions 3.20 and prior, EB-50GU-A: Versions 7.09 and prior, EW-50A: Versions 7.93 and prior and 18 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

  • CAPEC-221 Data Serialization External Entities Blowup

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits.

References

Check your stackJSON