cve.bz

CVE-2020-7562 schneider-electric: Out-of-bounds Read

8.1 highEPSS 0.9%

High (8.1) in schneider-electric. EPSS 0.9% estimated probability of exploitation activity in the next 30 days.

On this page
A CWE-125: Out-of-Bounds Read vulnerability exists in the Web Server on Modicon M340, Modicon Quantum and Modicon Premium Legacy offers and their Communication Modules (see notification for details) which could cause a segmentation fault or a buffer overflow when uploading a specially crafted file on the controller over FTP.

Severity

CVSS 3.1

8.1 high
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:H
EPSS
0.9% (unchanged from 0.9% a week ago; 0.9% 30 days ago) estimated probability of exploitation activity in the next 30 days; 61st percentile. Scored 2026-11-21. A forecast for this CVE across the internet, not for your own systems.
CISA's assessment (SSVC)
Exploitation: none · Automatable: no · Technical impact: partial, assessed 2026-05-29. From CISA's Vulnrichment in the CVE List: whether it is exploited, whether exploiting it can be automated, and how much control it gives.
CWE
CWE-125 Out-of-bounds Read
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2020-7562 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2020-7562?via=ask-ai-copy and https://cve.bz/cve/CVE-2020-7562?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2020-7562 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-21-005-01Schneider Electric Web Server on Modicon M3402021-01-05Commercial Facilities, Energy, Food and Agriculture, Government Facilities, Transportation Systems, Water and Wastewater SystemsM340 Communication Ethernet modules BMX NOE 0100 (H): all versions, M340 Communication Ethernet modules BMX NOE 0110 (H): all versions, Quantum communication modules 140NOC78x00: all versions and 9 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

  • CAPEC-540 Overread Buffers Likelihood: Low · Severity: High

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits.