cve.bz

CVE-2020-28397 siemens: Incorrect Authorization

5.3 mediumEPSS 0.8%Fix available

Medium (5.3) in siemens. EPSS 0.8% estimated probability of exploitation activity in the next 30 days.

On this page
A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7 PLCSIM Advanced (All versions > V2 < V4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (Version V4.4), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions > V2.5 < V2.9.2), SIMATIC S7-1500 Software Controller (All versions > V2.5 < V21.9), TIM 1531 IRC (incl. SIPLUS NET variants) (Version V2.1). Due to an incorrect authorization check in the affected component, an attacker could extract information about access protected PLC program variables over port 102/tcp from an affected device when reading multiple attributes at once.

Severity

CVSS 3.1

5.3 medium
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N
EPSS
0.8% (unchanged from 0.8% a week ago; 0.8% 30 days ago) estimated probability of exploitation activity in the next 30 days; 56th percentile. Scored 2026-11-21. A forecast for this CVE across the internet, not for your own systems.
CWE
CWE-863 Incorrect Authorization
OWASP Top 10
A01:2025 Broken Access Control
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2020-28397 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2020-28397?via=ask-ai-copy and https://cve.bz/cve/CVE-2020-28397?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2020-28397 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the NVD's CPE matches.

ProductAffected
siemens:cpu_1504d_tf_firmwarebefore 2.9.2
siemens:cpu_1507d_tf_firmwarebefore 2.9.2
siemens:cpu_1515sp_pc2_tf_firmwarebefore 21.9
siemens:simatic_s7_plcsim_advanced_firmwarefrom 2.0 before 4.0
siemens:simatic_s7-1500_software_controllerfrom 2.5 before 21.9
siemens:tim_1531_irc_firmware2.1
siemens:cpu_1211c_firmware4.4
siemens:cpu_1212c_firmware4.4
siemens:cpu_1212fc_firmware4.4
siemens:cpu_1214fc_firmware4.4
siemens:cpu_1214c_firmware4.4
siemens:cpu_1215fc_firmware4.4
siemens:cpu_1215c_firmware4.4
siemens:cpu_1217c_firmware4.4
siemens:siplus_cpu_1510sp_f-1pn_firmwarefrom 2.5 before 2.9.2
siemens:siplus_cpu_1511-1_pn_firmwarefrom 2.5 before 2.9.2
siemens:siplus_cpu_1511f-1_pn_firmwarefrom 2.5 before 2.9.2
siemens:siplus_cpu_1512sp-1_pn_firmwarefrom 2.5 before 2.9.2
siemens:siplus_cpu_1512sp_f-1pn_firmwarefrom 2.5 before 2.9.2
siemens:siplus_cpu_1513-1_pn_firmwarefrom 2.5 before 2.9.2
siemens:siplus_cpu_1513f-1_pn_firmwarefrom 2.5 before 2.9.2
siemens:siplus_cpu_1516-3_pn/dp_firmwarefrom 2.5 before 2.9.2
siemens:siplus_cpu-1516f-3_pn/dp_firmwarefrom 2.5 before 2.9.2
siemens:siplus_cpu_1518-4_pn/dp_firmwarefrom 2.5 before 2.9.2
siemens:siplus_cpu_1518f-4_pn/dp_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1510sp-1pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu1510sp_f-1_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1511-1pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1511c-1_pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1511f-1pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1511t-1pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1511tf-1pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1512c-1_pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1512sp-1_pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1512sp_f-1_pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1513-1_pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1513f-1_pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1513r-1_pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1513pro_f-2_pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1515-2_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1515f-2_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1515r-2_pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1515t-2_pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1515tf-2_pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1516pro_f-2_pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1516pro-2_pn_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1516-3_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1516f-3_firmwarefrom 2.5 before 2.9.2.
siemens:cpu_1516t-3_pn/dp_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1516tf-3_pn/dp_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1517-3_pn/dp_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1517f-3_pn/dp_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1517t-3_pn/dp_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1517tf-3_pn/dp_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1518-4_pn/dp_firmwarefrom 2.5 before 2.9.2
siemens:cpu_1518f-4_pn/dp_firmwarefrom 2.5 before 2.9.2

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-21-257-23Siemens SIMATIC and TIM2021-08-10MultipleSIMATIC Drive Controller family, SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants), SIMATIC S7 PLCSIM Advanced and 4 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

References

Check your stackJSON