cve.bz

CVE-2020-15782 siemens

9.8 criticalEPSS 5.2%Fix available

Critical (9.8) in siemens. EPSS 5.2% estimated probability of exploitation activity in the next 30 days.

On this page
A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SINAMICS PERFECT HARMONY GH180 Drives (Drives manufactured before 2021-08-13), SINUMERIK MC (All versions < V6.15), SINUMERIK ONE (All versions < V6.15). Affected devices are vulnerable to a memory protection bypass through a specific operation. A remote unauthenticated attacker with network access to port 102/tcp could potentially write arbitrary data and code to protected memory areas or read sensitive data to launch further attacks.

Severity

CVSS 3.1

9.8 critical
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
EPSS
5.2% (unchanged from 5.2% a week ago; 5.2% 30 days ago) estimated probability of exploitation activity in the next 30 days; 93rd percentile. Scored 2026-11-21. A forecast for this CVE across the internet, not for your own systems.
CISA's assessment (SSVC)
Exploitation: none · Automatable: yes · Technical impact: total, assessed 2026-06-02. From CISA's Vulnrichment in the CVE List: whether it is exploited, whether exploiting it can be automated, and how much control it gives.
CWE
CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2020-15782 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2020-15782?via=ask-ai-copy and https://cve.bz/cve/CVE-2020-15782?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2020-15782 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the NVD's CPE matches.

ProductAffected
siemens:simatic_driver_controller_firmwarebefore 2.9.2
siemens:s7-1200_cpu_firmwarebefore 4.5.0
siemens:s7-1500_cpu_firmwarebefore 2.9.2
siemens:simatic_s7-plcsim_advancedbefore 4.0

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-25-182-01FESTO Didactic CP, MPS 200, and MPS 400 Firmware2024-09-09Critical manufacturingSiemens Simatic S7-1500 / ET200SP < V2.9.2 installed on FESTO Didactic CP including S7 PLC, Siemens Simatic S7-1500 / ET200SP < V2.9.2 installed on FESTO Didactic MPS 200 Systems, Siemens Simatic S7-1500 / ET200SP < V2.9.2 installed on FESTO Didactic MPS 400 SystemsSiemens Simatic S7-1500 / ET200SP V2.9.2 installed on FESTO Didactic CP including S7 PLC, Siemens Simatic S7-1500 / ET200SP V2.9.2 installed on FESTO Didactic MPS 200 Systems, Siemens Simatic S7-1500 / ET200SP V2.9.2 installed on FESTO Didactic MPS 400 Systems
ICSA-21-194-13Siemens SINAMICS PERFECT HARMONY GH180 (Update A)2021-07-13Critical Manufacturing, EnergySINAMICS PERFECT HARMONY GH180 Drives: manufactured before 2021-8-13, SINAMICS PERFECT HARMONY model 6SR4: with option W41 with X30 air to air hex, SINAMICS PERFECT HARMONY model 6SR5: with options A84 A85 E06 W41 with X30 air to air hexnone listed
ICSA-21-194-17Siemens SINUMERIK ONE and SINUMERIK MC (Update A)2021-07-13MultipleSINUMERIK MC, SINUMERIK ONEnone listed
ICSA-21-152-01Siemens SIMATIC S7-1200 and S7-1500 CPU Families (Update A)2021-05-28MultipleSIMATIC Drive Controller family, SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) and 4 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.