cve.bz

CVE-2019-6855 schneider-electric: Incorrect Authorization

7.3 highEPSS 1.0%

High (7.3) in schneider-electric. EPSS 1.0% estimated probability of exploitation activity in the next 30 days.

On this page
Incorrect Authorization vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20) , and Modicon M580 (all versions prior to V3.10), which could cause a bypass of the authentication process between EcoStruxure Control Expert and the M340 and M580 controllers.

Severity

CVSS 3.1

7.3 high
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L
EPSS
1.0% (unchanged from 1.0% a week ago; 1.0% 30 days ago) estimated probability of exploitation activity in the next 30 days; 62nd percentile. Scored 2026-11-21. A forecast for this CVE across the internet, not for your own systems.
CWE
CWE-863 Incorrect Authorization
OWASP Top 10
A01:2025 Broken Access Control
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2019-6855 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2019-6855?via=ask-ai-copy and https://cve.bz/cve/CVE-2019-6855?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2019-6855 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the NVD's CPE matches.

ProductAffected
schneider-electric:ecostruxure_control_expertbefore 14.1
schneider-electric:ecostruxure_control_expert14.1
schneider-electric:modicon_m580_bmep584040_firmwarebefore 3.10
schneider-electric:modicon_m580_bmeh584040_firmwarebefore 3.10
schneider-electric:modicon_m580_bmep586040_firmwarebefore 3.10
schneider-electric:modicon_m580_bmeh586040_firmwarebefore 3.10
schneider-electric:modicon_m580_bmep581020_firmwarebefore 3.10
schneider-electric:modicon_m580_bmep582020_firmwarebefore 3.10
schneider-electric:modicon_m580_bmep582040_firmwarebefore 3.10
schneider-electric:modicon_m580_bmep583020_firmwarebefore 3.10
schneider-electric:modicon_m580_bmep583040_firmwarebefore 3.10
schneider-electric:modicon_m580_bmep584020_firmwarebefore 3.10
schneider-electric:modicon_m580_bmep585040_firmwarebefore 3.10
schneider-electric:modicon_m580_bmeh582040_firmwarebefore 3.10
schneider-electric:modicon_m580_bmep584040s_firmwarebefore 3.10
schneider-electric:modicon_m580_bmeh584040s_firmwarebefore 3.10
schneider-electric:modicon_m580_bmeh586040s_firmwarebefore 3.10
schneider-electric:modicon_m580_bmep582040s_firmwarebefore 3.10
schneider-electric:modicon_m340_bmxp3420302_firmwarebefore 3.20
schneider-electric:modicon_m340_bmxp342020_firmwarebefore 3.20
schneider-electric:modicon_m340_bmxp342000_firmwarebefore 3.20
schneider-electric:modicon_m340_bmxp341000_firmwarebefore 3.20
schneider-electric:modicon_m340_bmxp3420102_firmwarebefore 3.20

References

Check your stackJSON