cve.bz

CVE-2019-6572

9.1 criticalEPSS 2.7%

A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15.1 Update 1), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15.1 Update 1), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Update 1), SIMATIC WinCC Runtime Professional (All versions < V15.1 Update 1), SIMATIC WinCC (TIA Portal) (All versions < V15.1 Update 1), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The affected device offered SNMP read and write capacities with a publicly know hardcoded community string. The security vulnerability could be exploited by an attacker with network access to the affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.

Severity

CVSS 3.1

9.1 critical
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N
EPSS
2.7% chance of exploitation in the next 30 days; higher than 86% of CVEs (scores of 2026-10-31)
CWEs
CWE-798, CWE-200
Published
Modified
Record from
the NVD, synced

Affected

References

Check your stackJSON