cve.bz

CVE-2019-19282 siemens: Incorrect Calculation of Buffer Size

7.5 highEPSS 1.3%

High (7.5) in siemens. EPSS 1.3% estimated probability of exploitation activity in the next 30 days.

On this page
A vulnerability has been identified in OpenPCS 7 V8.1 (All versions), OpenPCS 7 V8.2 (All versions), OpenPCS 7 V9.0 (All versions < V9.0 Upd3), SIMATIC BATCH V8.1 (All versions), SIMATIC BATCH V8.2 (All versions < V8.2 Upd12), SIMATIC BATCH V9.0 (All versions < V9.0 SP1 Upd5), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC NET PC Software V16 (All versions < V16 Update 1), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP3), SIMATIC Route Control V8.1 (All versions), SIMATIC Route Control V8.2 (All versions), SIMATIC Route Control V9.0 (All versions < V9.0 Upd4), SIMATIC WinCC (TIA Portal) V13 (All versions < V13 SP2), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Update 10), SIMATIC WinCC (TIA Portal) V15.1 (All versions < V15.1 Update 5), SIMATIC WinCC (TIA Portal) V16 (All versions < V16 Update 1), SIMATIC WinCC V7.3 (All versions), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 14), SIMATIC WinCC V7.5 (All versions < V7.5 SP1 Update 1). Through specially crafted messages, when encrypted communication is enabled, an attacker with network access could use the vulnerability to compromise the availability of the system by causing a Denial-of-Service condition. Successful exploitation requires no system privileges and no user interaction.

Severity

CVSS 3.1

7.5 high
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS
1.3% (unchanged from 1.3% a week ago; 1.3% 30 days ago) estimated probability of exploitation activity in the next 30 days; 72nd percentile. Scored 2026-11-21. A forecast for this CVE across the internet, not for your own systems.
CWE
CWE-131 Incorrect Calculation of Buffer Size
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2019-19282 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2019-19282?via=ask-ai-copy and https://cve.bz/cve/CVE-2019-19282?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2019-19282 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the NVD's CPE matches.

ProductAffected
siemens:openpcs_79.0
siemens:openpcs_79.0_update_1
siemens:simatic_batch9.0
siemens:simatic_batch9.0:sp1
siemens:simatic_batch9.0:sp1_update_1
siemens:simatic_batch9.0:sp1_update_2
siemens:simatic_batch9.0:sp1_update_3
siemens:simatic_batch9.0:sp1_update_4
siemens:simatic_net_pcbefore 16
siemens:simatic_net_pc16
siemens:simatic_pcs_78.1
siemens:simatic_pcs_78.2
siemens:simatic_pcs_79.0
siemens:simatic_pcs_79.0:sp1
siemens:simatic_pcs_79.0:sp2
siemens:simatic_route_controlbefore 9.0
siemens:simatic_route_control9.0
siemens:simatic_wincc7.4
siemens:simatic_wincc7.4:sp1
siemens:simatic_wincc7.4:sp1_update_1
siemens:simatic_wincc7.4:sp1_update_10
siemens:simatic_wincc7.4:sp1_update_11
siemens:simatic_wincc7.4:sp1_update_12
siemens:simatic_wincc7.4:sp1_update_13
siemens:simatic_wincc7.4:sp1_update_2
siemens:simatic_wincc7.4:sp1_update_3
siemens:simatic_wincc7.4:sp1_update_4
siemens:simatic_wincc7.4:sp1_update_5
siemens:simatic_wincc7.4:sp1_update_6
siemens:simatic_wincc7.4:sp1_update_7
siemens:simatic_wincc7.4:sp1_update_8
siemens:simatic_wincc7.4:sp1_update_9
siemens:simatic_wincc7.5
siemens:simatic_wincc7.5:sp1
siemens:simatic_wincc7.5.1
siemens:simatic_wincc13
siemens:simatic_wincc13:sp1
siemens:simatic_wincc14.0.1
siemens:simatic_wincc15.1
siemens:simatic_wincc15.1:update_1
siemens:simatic_wincc15.1:update_2
siemens:simatic_wincc15.1:update_3
siemens:simatic_wincc15.1:update_4
siemens:simatic_wincc16

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-20-042-06Siemens SIMATIC PCS 7, SIMATIC WinCC, and SIMATIC NET PC (Update G)2020-02-11MultipleOpenPCS 7 V8.1, OpenPCS 7 V8.2, OpenPCS 7 V9.0 and 19 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

  • CAPEC-47 Buffer Overflow via Parameter Expansion Likelihood: Medium · Severity: High
  • CAPEC-100 Overflow Buffers Likelihood: High · Severity: Very High

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits.

References

Check your stackJSON