cve.bz

CVE-2019-18336 siemens: Uncontrolled Resource Consumption

7.5 highEPSS 1.7%

High (7.5) in siemens. EPSS 1.7% estimated probability of exploitation activity in the next 30 days.

On this page
A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V3.X.17), SIMATIC TDC CP51M1 (All versions < V1.1.8), SIMATIC TDC CPU555 (All versions < V1.1.1), SINUMERIK 840D sl (All versions < V4.8.6), SINUMERIK 840D sl (All versions < V4.94). Specially crafted packets sent to port 102/tcp (Profinet) could cause the affected device to go into defect mode. A restart is required in order to recover the system. Successful exploitation requires an attacker to have network access to port 102/tcp, with no authentication. No user interation is required. At the time of advisory publication no public exploitation of this security vulnerability was known.

Severity

CVSS 3.1

7.5 high
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
EPSS
1.7% (unchanged from 1.7% a week ago; 1.7% 30 days ago) estimated probability of exploitation activity in the next 30 days; 78th percentile. Scored 2026-11-21. A forecast for this CVE across the internet, not for your own systems.
CISA's assessment (SSVC)
Exploitation: none · Automatable: yes · Technical impact: partial, assessed 2026-06-02. From CISA's Vulnrichment in the CVE List: whether it is exploited, whether exploiting it can be automated, and how much control it gives.
CWE
CWE-400 Uncontrolled Resource Consumption
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2019-18336 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2019-18336?via=ask-ai-copy and https://cve.bz/cve/CVE-2019-18336?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2019-18336 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the NVD's CPE matches.

ProductAffected
siemens:simatic_s7-300_cpu_firmwarebefore 3.3.17
siemens:simatic_s7-300_cpu_312_ifm_firmwarebefore 3.3.17
siemens:simatic_s7-300_cpu_313_firmwarebefore 3.3.17
siemens:simatic_s7-300_cpu_314_firmwarebefore 3.3.17
siemens:simatic_s7-300_cpu_314_ifm_firmwarebefore 3.3.17
siemens:simatic_s7-300_cpu_315_firmwarebefore 3.3.17
siemens:simatic_s7-300_cpu_315-2_dp_firmwarebefore 3.3.17
siemens:simatic_s7-300_cpu_316-2_dp_firmwarebefore 3.3.17
siemens:simatic_s7-300_cpu_318-2_firmwarebefore 3.3.17
siemens:sinumerik_840d_slbefore 4.8.6
siemens:sinumerik_840d_slbefore 4.94
siemens:simatic_tdc_cp51m1_firmwarebefore 1.1.8
siemens:simatic_tdc_cpu555_firmwarebefore 1.1.1

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-20-070-02Siemens SIMATIC S7-300 CPUs and SINUMERIK Controller over Profinet (Update A)2020-03-10MultipleSiemens SIMATIC S7-300 CPU family (incl.'related ET200 CPUs and SIPLUS variants): All versions < V3.X.17, Siemens SIMATIC TDC CP51M1: All versions < V1.1.8, Siemens SIMATIC TDC CPU555: All versions < V1.1.1 and 2 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

  • CAPEC-147 XML Ping of the Death Likelihood: Low · Severity: Medium
  • CAPEC-227 Sustained Client Engagement
  • CAPEC-492 Regular Expression Exponential Blowup

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits.

References

Check your stackJSON