CVSS 4.0
7.1 highCVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:L/VA:H/SC:N/SI:N/SA:NHigh (7.1) in siemens. EPSS 0.7% estimated probability of exploitation activity in the next 30 days.
CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:L/VA:H/SC:N/SI:N/SA:NCVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:HExplain CVE-2019-13939 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2019-13939?via=ask-ai-copy and https://cve.bz/cve/CVE-2019-13939?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2019-13939 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.
From the CNA's record in the CVE List.
| Product | Affected |
|---|---|
| Siemens APOGEE MEC/MBC/PXC (P2) | All versions < V2.8.2 |
| Siemens APOGEE PXC Compact (BACnet) | before V3.5.3 |
| Siemens APOGEE PXC Compact (P2 Ethernet) | from V2.8.2 before V2.8.19 |
| Siemens APOGEE PXC Modular (BACnet) | before V3.5.3 |
| Siemens APOGEE PXC Modular (P2 Ethernet) | from V2.8.2 before V2.8.19 |
| Siemens Capital Embedded AR Classic 431-422 | all versions |
| Siemens Capital Embedded AR Classic R20-11 | before V2303 |
| Siemens Desigo PXC00-E.D | from V2.3 before V6.0.327 |
| Siemens Desigo PXC00-U | All versions >= V2.3x and < V6.00.327 |
| Siemens Desigo PXC001-E.D | from V2.3 before V6.0.327 |
| Siemens Desigo PXC100-E.D | from V2.3 before V6.0.327 |
| Siemens Desigo PXC12-E.D | from V2.3 before V6.0.327 |
| Siemens Desigo PXC128-U | All versions >= V2.3x and < V6.00.327 |
| Siemens Desigo PXC200-E.D | from V2.3 before V6.0.327 |
| Siemens Desigo PXC22-E.D | from V2.3 before V6.0.327 |
| Siemens Desigo PXC22.1-E.D | from V2.3 before V6.0.327 |
| Siemens Desigo PXC36.1-E.D | from V2.3 before V6.0.327 |
| Siemens Desigo PXC50-E.D | from V2.3 before V6.0.327 |
| Siemens Desigo PXC64-U | All versions >= V2.3x and < V6.00.327 |
| Siemens Desigo PXM20-E | from V2.3 before V6.0.327 |
| Siemens Nucleus NET | all versions |
| Siemens Nucleus ReadyStart V3 | before V2017.02.3 |
| Siemens Nucleus Source Code | all versions |
| Siemens SIMOTICS CONNECT 400 | All versions < V0.3.0.330 |
| Siemens TALON TC Compact (BACnet) | before V3.5.3 |
| Siemens TALON TC Modular (BACnet) | before V3.5.3 |
| Advisory | Title | Published | Sectors | Affected | Fixed |
|---|---|---|---|---|---|
| ICSA-20-105-06 | Siemens SIMOTICS, Desigo, APOGEE, and TALON | 2020-04-14 | Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems | APOGEE MEC/MBC/PXC (P2), APOGEE PXC Compact (BACnet), APOGEE PXC Compact (P2 Ethernet) and 18 more | none listed |
| ICSA-19-318-01 | Siemens Mentor Nucleus Networking Module | 2019-11-12 | Critical Manufacturing, Transportation Systems, Energy, Healthcare and Public Health, Financial Services, Government Services and Facilities | Capital Embedded AR Classic 431-422, Capital Embedded AR Classic R20-11, Nucleus NET and 2 more | none listed |
From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.
The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits. More on the page of CWE-20 (51).