cve.bz

CVE-2018-4858 siemens: Improper Access Control

7.8 highEPSS 1.8%

High (7.8) in siemens. EPSS 1.8% estimated probability of exploitation activity in the next 30 days.

On this page
A vulnerability has been identified in IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (affected as IEC 61850 system configurator is incorporated) (All versions < V7.80), DIGSI 4 (All versions < V4.93), SICAM PAS/PQS (All versions < V8.11), SICAM PQ Analyzer (All versions < V3.11), SICAM SCC (All versions < V9.02 HF3). A service of the affected products listening on all of the host's network interfaces on either port 4884/TCP, 5885/TCP, or port 5886/TCP could allow an attacker to either exfiltrate limited data from the system or to execute code with Microsoft Windows user permissions. Successful exploitation requires an attacker to be able to send a specially crafted network request to the vulnerable service and a user interacting with the service's client application on the host. In order to execute arbitrary code with Microsoft Windows user permissions, an attacker must be able to plant the code in advance on the host by other means. The vulnerability has limited impact to confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.

Severity

CVSS 3.1

7.8 high
CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H
EPSS
1.8% (unchanged from 1.8% a week ago; 1.8% 30 days ago) estimated probability of exploitation activity in the next 30 days; 79th percentile. Scored 2026-11-22. A forecast for this CVE across the internet, not for your own systems.
CWE
CWE-284 Improper Access Control
OWASP Top 10
A01:2025 Broken Access Control
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2018-4858 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2018-4858?via=ask-ai-copy and https://cve.bz/cve/CVE-2018-4858?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2018-4858 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the NVD's CPE matches.

ProductAffected
siemens:ec_61850_system_configurator_firmwarebefore 5.80
siemens:sicam_pq_analyzer_firmwarebefore 3.11
siemens:digsi_5_firmwarebefore 7.80
siemens:sicam_pas/pqsbefore 8.11

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-18-317-01ICSA-18-317-01 Siemens IEC 61850 System Configurator, DIGSI 5, DIGSI 4, SICAM PAS/PQS, SICAM PQ Analyzer, and SICAM SCC2018-06-26MultipleIEC 61850 system configurator, DIGSI 5 (affected as IEC 61850 system configurator is incorporated), DIGSI 4 and 3 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits. More on the page of CWE-284 (17).

References

Check your stackJSON