cve.bz

CVE-2018-4838 siemens

7.5 highEPSS 1.4%Fix available

High (7.5) in siemens. EPSS 1.4% estimated probability of exploitation activity in the next 30 days.

On this page
A vulnerability has been identified in EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module DNP3 variant (All versions < V1.04), EN100 Ethernet module PROFINET IO variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module IEC 104 variant (All versions < V1.22). The web interface (TCP/80) of affected devices allows an unauthenticated user to upgrade or downgrade the firmware of the device, including to older versions with known vulnerabilities.

Severity

CVSS 3.0

7.5 high
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N
EPSS
1.4% (unchanged from 1.4% a week ago; 1.4% 30 days ago) estimated probability of exploitation activity in the next 30 days; 73rd percentile. Scored 2026-11-22. A forecast for this CVE across the internet, not for your own systems.
CWE
CWE-306 Missing Authentication for Critical Functionality
OWASP Top 10
A07:2025 Authentication Failures
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Fix and patched versions

Ask an AI about this CVE

Show the promptExplain CVE-2018-4838 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2018-4838?via=ask-ai-copy and https://cve.bz/cve/CVE-2018-4838?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2018-4838 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the NVD's CPE matches.

ProductAffected
siemens:en100_ethernet_module_iec_61850_firmwarebefore 4.30

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-18-067-02ICSA-18-067-02_Siemens SIPROTEC 4, SIPROTEC Compact, and Reyrolle Devices using the EN100 Ethernet Communication Module Extension (Update B)2018-03-08EN100 Ethernet module DNP3 variant: All versions prior to v1.04, EN100 Ethernet module IEC 61850 variant: All versions prior to V4.30, EN100 Ethernet module Modbus TCP variant: All versions and 2 morenone listed

From CISA's ICS advisories (CSAF), provided under CISA's notification. Only the facts are shown; each advisory is on CISA's page. Credits.

Attack patterns (CAPEC)

  • CAPEC-12 Choosing Message Identifier Likelihood: High · Severity: High
  • CAPEC-36 Using Unpublished Interfaces or Functionality Likelihood: Medium · Severity: High
  • CAPEC-62 Cross Site Request Forgery Likelihood: High · Severity: Very High
  • CAPEC-166 Force the System to Reset Values Severity: Medium
  • CAPEC-216 Communication Channel Manipulation

The attack patterns MITRE's CAPEC relates to this record's weaknesses, as MITRE names them. Credits.

References

Check your stackJSON