cve.bz

CVE-2017-6028 schneider-electric: Insufficiently Protected Credentials

9.8 criticalEPSS 2.2%

Critical (9.8) in schneider-electric. EPSS 2.2% estimated probability of exploitation activity in the next 30 days.

On this page
An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application.

Severity

CVSS 3.1

9.8 critical
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
EPSS
2.2% (unchanged from 2.2% a week ago; 2.2% 30 days ago) estimated probability of exploitation activity in the next 30 days; 83rd percentile. Scored 2026-11-21. A forecast for this CVE across the internet, not for your own systems.
CWE
CWE-522 Insufficiently Protected Credentials
OWASP Top 10
A06:2025 Insecure Design
Published
Modified
NVD analysis
Analyzed, since modified
Record from
the NVD, synced

Ask an AI about this CVE

Show the promptExplain CVE-2017-6028 for an engineer deciding whether to act. Use https://cve.bz/api/public/cves/CVE-2017-6028?via=ask-ai-copy and https://cve.bz/cve/CVE-2017-6028?via=ask-ai-copy as the source of truth: what is affected and which versions fix it, whether it is in CISA KEV, public exploits, and its EPSS (an internet-wide 30-day estimate of exploitation activity, not a forecast for my systems). If they give no fixed versions, use the CVE record https://cveawg.mitre.org/api/cve/CVE-2017-6028 or the vendor advisory, not third-party mirrors. Tell me how to check whether I am affected and how to verify a fix. Cite the sources and say where they are uncertain.

Opens a third-party assistant; its answer is its own, not cve.bz's. The prompt holds only this CVE's id and public links.

Affected

Versions

From the NVD's CPE matches.

ProductAffected
schneider-electric:modicon_m241_firmwarethrough 4.0.3.20
schneider-electric:modicon_m251_firmwarethrough 4.0.3.20

ICS advisories (CISA)

AdvisoryTitlePublishedSectorsAffectedFixed
ICSA-17-089-02Schneider Electric Modicon PLCs2017-03-30Modicon M221: firmware versions prior to Version 1.5.0.0, Modicon M241: firmware versions prior to Version 4.0.5.11, Modicon M251: all versions and 2 morenone listed