{"cve":"CVE-2025-11782","nvd":{"published":"2025-12-02T13:15:49.420","modified":"2026-09-26T00:10:00.127","status":"Analyzed","description":"Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2. The 'ShowDownload()' function uses “sprintf()” to format a string that includes the user-controlled input of 'GetParameter(meter)' in the fixed-size buffer 'acStack_4c' (64 bytes) without checking the length. An attacker can provide an excessively long value for the 'meter' parameter that exceeds the 64-byte buffer size.","cvss_v4":{"vector":"CVSS:4.0/AV:A/AC:L/AT:N/PR:L/UI:N/VC:H/VI:L/VA:H/SC:H/SI:L/SA:H","score":8.5},"cvss_v3":{"version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H","score":9.8},"cwes":["CWE-121"],"references":["https://www.incibe.es/en/incibe-cert/notices/aviso-sci/multiple-vulnerabilities-circutor-products-0"],"products":["circutor:sge-plc1000_firmware","circutor:sge-plc50_firmware"],"source":"nvd","synced_at":"2026-10-19T22:16:02.354564667+00:00"},"epss":{"cve":"CVE-2025-11782","score":0.00372,"percentile":0.31205,"date":"2026-11-01"},"kev":null,"osv":[],"attribution":["This product uses the NVD API but is not endorsed or certified by the NVD.","EPSS scores: FIRST Exploit Prediction Scoring System, https://www.first.org/epss","Known exploited vulnerabilities: CISA Known Exploited Vulnerabilities Catalog, https://www.cisa.gov/known-exploited-vulnerabilities-catalog","Package advisories: OSV (https://osv.dev), from the GitHub Advisory Database, PyPA, Go, RustSec and other ecosystem databases, under CC-BY 4.0 or CC0","CVE records: the CVE Program's CVE List (https://www.cve.org), under its terms of use (https://www.cve.org/Legal/TermsOfUse). CVE is a registered trademark of The MITRE Corporation; this product is not affiliated with the CVE Program."]}